  • 1.  Vison Frame Fans

    Posted 06-28-2016 15:11
    can anyone tell me at what point the Vision's frame will shutdown, due to overheating,or at least kick the cooling fans in at a higher speed,
    the reason is we had an Air Conditioner trip on us this morning so the server room was hot,after getting air working,it took a long time to get the room cool again, during the time
    I checked the status screen for the vision, it said inlet air temp was 35 Celsius
    which is 95 degrees Fahrenheit,fan speed was running 50% all of this was after the air was fixed,
    so really hot still
    is there a heat threshold?
    are the fans on a sensor that will speed them up when it is too hot to operate?



  • 2.  RE: Vison Frame Fans

    Posted 06-29-2016 21:26
    Fan speeds will increase as the temperature of the boards increases. So even with the inlet temp at 35 the system FPGAs were still running a temperatures that did not require the "speeding" up of the fans.

    There are sensors on all MEs and also the main CPU card that track the temperatures.
    #Vision


  • 3.  RE: Vison Frame Fans

    Posted 05-05-2017 00:59
    I'm new to the vision switcher, we are wanting to use the chassis and switcher together in a conference room environment, however the fans are so loud. Almost like they are running at full speed however the status indicates they are running at 33% is this normal? Should this switcher and panel be separated in a server room/control room environment?
    #Vision


  • 4.  RE: Vison Frame Fans

    Posted 05-05-2017 02:32
    Yes these are meant to be in separate rooms -- usually there is a rack/equipment room where the video processing goes.