  • 1.  GPIO Voltage Question

    Posted 02-01-2017 02:58
    I admit right in the beginning that I don't fully understand the ins and outs (no pun intended) of GPIO things. It seems like it would be fairly simple, but there are some things that are confusing me.

    We have a Ross Carbonite Multimedia frame and in another room we have some Grass Valley products. We have a GV switcher and some GV T2 iDDRs. We are using the GV Switcher to fire play commands via GPIOs. (We know we can control them directly through LAN controls, and we do that as well, but we have another need which uses GPIOs). I'm wanting to hook the Ross switcher into these T2s to do the same thing. The T2s have the GPI as an input, and accept contact closure. I have measured both the GV and the Ross with a multimeter and the GV does not output any voltage with it's GPOs. The Ross, no matter what settings you use, outputs 5V. Is there a way to set the Ross to output a contact closure only? We (and the people at GV) are worried about the 5V breaking something in the T2s. Which doesn't entirely make sense to me, to be honest, but that's what their saying.

    And if not, do you guys know of a way we can get a contact closure with another box that accepts 5V like a relay or something?

    Thanks for any help you can provide! Forgive me if I'm misunderstanding something.

    -Tyler


  • 2.  RE: GPIO Voltage Question

    Posted 02-01-2017 03:23
    Yes so the T2 does not really accept a GPO. They want a short to ground. So what you will want to do is use a "tally" connection from the switcher and then set the rule up to be a source on an Aux that you don't use -- so it's virtual.

    Then build a Custom Control that sets the source on to the Aux. Then pause for like 5 frames then set the Aux back to black. This will give you a 5 frame short. If that does not trigger it consistently increase the pause until you get the consistent result.

    Les
    #Carbonite


  • 3.  RE: GPIO Voltage Question

    Posted 02-01-2017 04:10
    Interesting... I'll give that a shot and see what happens! Thanks for the quick reply!
    #Carbonite


  • 4.  RE: GPIO Voltage Question

    Posted 02-06-2017 18:56
    I would call tech support. They will be able to help trouble shoot this to fix it.
    #Carbonite


  • 5.  RE: GPIO Voltage Question

    Posted 09-25-2017 02:09
    This post is long past but here's another option that is handy to know about.
    Henry Engineering makes a little box called LogicConverter that will take your GPO's from the Ross and convert them to latched or momentary contact closures on relays.
    I've found it very useful in a number of occassions.